Daily Time Control with Simple Operations

DO YOU NEED SUPPORT ?

Digital Daily Time Switch OMRON H5F

Ngan Anh Phat Co., Ltd specializes in providing genuine  products Digital Daily Time Switch OMRON H5F from the manufacturer Omron, originating from Japan, to the Vietnamese market.


Outstanding features of the Digital Daily Time Switch OMRON H5F:

• Specify the operation days.
(However, you can set only one pattern of operation days and specified days.) 

• Up to 12 ON/OFF operations (24 for pulse-output operation). 

• Special holidays can be handled easily with the holiday setting function. 

• Adjustments for sudden schedule changes can be made easily using output override and automatic return operation. 

• The operation program can be checked easily with the program check function. 

• Enables pulse output operation and summer time setting. 

• Incorporates finger-safe terminals. 

• Conforms to UL, CSA, and CE marking. 

• Meets a variety of mounting requirements: flush mounting, surface mounting, and DIN track mounting.

Specifications

Ratings

Rated supply voltage 100 to 240 VAC (50/60 Hz)
Operating voltage range 85% to 110% of rated supply voltage
Power consumption Approx. 2.4 VA at 264 VAC
Control outputs Contact output: SPST-NO, 15 A at 250 VAC, resistive load, 10 A at 24 VDC, resistive load
Minimum applied load: 100 mA at 5 VDC (failure level: P, reference value)
NEMA A300 Pilot Duty, 1/3 HP at 120 VAC
External connections Screw terminals (M3.5 screw)
Terminal screw
tightening torque
0.98 to 1.17 Nm

 

Characteristics

Accuracy of
operating time
±0.01% ±0.05 s max. *1
Setting error
Influence of voltage
Influence of
temperature
Influence of EMS.
(at EN61326-1)
Time accuracy ±15 s per month (at 25°C)
Memory protection Continuous use: 5 years min. (at 25°C); Power-interruption rate of 50%: 10 years min. (at
25°C) *2 (lithium battery)
Insulation resistance 100 MΩ min. (between current-carrying terminals and exposed non-current-carrying metal
parts, between operating power supply circuit and control output circuit and between non-
continuous contacts)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between current-carrying terminals and exposed non-
current-carrying metal parts and between operating power supply circuit and control output
circuit)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
Noise immunity 1.5 kV (between power terminals)
Square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)
Vibration resistance Destruction:10 to 55 Hz with 0.375-mm single amplitude, four cycles each in three directions
(8 minutes per cycle)
Malfunction:10 to 55 Hz with 0.25-mm single amplitude for 10 minutes each in three directions
Shock resistance Destruction:300 m/s2 3 times each in 6 directions
Malfunction:100 m/s2 3 times each in 6 directions
Ambient temperature Operating: -10°C to 55°C (with no icing)
Storage: -25°C to 65°C (with no icing)
Ambient humidity Operating: 35% to 85%
Life expectancy Mechanical (at 20°C):
100,000 operations min.
Electrical (at 20°C):
50,000 operations min. (15 A, 250 VAC, resistive load)
50,000 operations min. (1 HP, 250 VAC, motor load)
50,000 operations min. (10 A, 250 VAC, inductive load (cosφ = 0.7))
50,000 operations min. (100 W, 100 VAC, lamp load)
10,000 operations min. (300 W, 100 VAC, lamp load)
Approved safety
standards
UL508/Listing, CSA C22.2 No. 14, conforms to EN61010-1 (Pollution degree 2/overvoltage
category II)
Conforms to VDE0106/P100 (finger protection).
Conforms to Electrical Appliance and Material Safety Law (for Japan)
EMC (EMI) EN61326-1 *3
Emission Enclosure: EN55011 Group 1 class A
Emission AC mains: EN55011 Group 1 class A
(EMS) EN61326-1 *3
Immunity ESD: EN61000-4-2: 4 kV contact discharge (level 2); 8 kV air discharge (level 3)
Immunity RF-interference: EN61000-4-3: 10 V/m (Amplitude-modulated, 80 MHz to 1 GHz,
1.4 to 2 GHz) (level 3)
Immunity Conducted
Disturbance: EN61000-4-6: 10 V (0.15 to 80 MHz) (according to EN61000-6-2)
Immunity Burst: EN61000-4-4: 2 kV power-line (level 3); 1 kV I/O signal-line (level 4)
Immunity Surge: EN61000-4-5: 1 kV line to lines (power and output lines) (level 2); 2 kV line to
ground (power and output lines) (level 3)
Immunity Voltage Dip/Interruption: EN61000-4-11: 0.5 cycle, 100% (rated voltage)
Immunity Magnetic Power Field: EN61000-4-8: 30 A/m
Case color Light gray (Munsell 5Y7/1)
Weight H5F-B: approx. 115 g; H5F-KB: approx. 160 g; H5F-FB: approx. 130 g

*1. The total error including the repeat accuracy, setting error, variation due to voltage change, and variation due to
       temperature change is ±0.01%±0.05 s max. ±0.01% also indicates an error in the time interval of a set time.
*2. The total time when power is not being supplied.
*3. Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)