Compact, Slim-profile SSRs with Heat Sinks. Solid State Contactors for Three-phase Heaters Reduced Installation Work with DIN Track Mounting.
Ngan Anh Phat Co., Ltd specializes in providing genuine products Solid State Contactors for Heaters G3PE OMRON (3 phase) from the manufacturer Omron, originating from Japan, to the Vietnamese market.
• RoHS compliant.
• Surge pass protection improved surge dielectric strength for output currents. (OMRON testing)
• Slim design with 3-phase output and built-in heat sinks.
• DIN Track mounting types and screw mounting types are available. All DIN Track mounting types mount to DIN Track
(applicable DIN Track: TR35-15Fe (IEC 60715)).
• Conforms to UL, CSA, and EN standards (TÜV certification).
UL508, CSA22.2 No.14, and EN60947-4-3
Model | Same for all models |
---|---|
Rated operating voltage | 12 to 24 VDC |
Operating voltage range | 9.6 to 30 VDC |
Rated input current (impedance) | 10 mA max. (24 VDC) |
Must-operate voltage | 9.6 VDC max. |
Must-release voltage | 1 VDC min. |
Insulation method | Phototriac |
Operation indicator | Yellow LED |
Model | G3PE- 215B- 3(N) |
G3PE- 215B- 2(N) |
G3PE- 225B- 3(N) |
G3PE- 225B- 2(N) |
G3PE- 235B- 3(N) |
G3PE- 235B- 2(N) |
G3PE- 245B- 3(N) |
G3PE- 245B- 2(N) |
---|---|---|---|---|---|---|---|---|
Rated load voltage | 100 to 240 VAC | |||||||
Operating voltage range | 75 to 264 VAC | |||||||
Rated load current *1 | 15 A (at 40 ° C) | 25 A (at 40 ° C) | 35 A (at 25 ° C) | 45 A (at 25 ° C) | ||||
Minimum load current | 0.2 A | 0.5 A | ||||||
Inrush current resistance (peak value) |
150 A (60 Hz, 1 cycle) |
220 A (60 Hz, 1 cycle) |
440 A (60 Hz, 1 cycle) |
|||||
Permissible I2t (reference value) | 121A2s | 260A2s | 1,260A2s | |||||
Applicable load (resistive load: AC1 class) *2 |
5.1 kW (at 200 VAC) |
8.6 kW (at 200 VAC) |
12.1 kW (at 200 VAC) |
15.5 kW (at 200 VAC) |
Model | G3PE- 515B- 3(N) |
G3PE- 515B- 2(N) |
G3PE- 525B- 3(N) |
G3PE- 525B- 2(N) |
G3PE- 535B- 3(N) |
G3PE- 535B- 2(N) |
G3PE- 545B- 3(N) |
G3PE- 545B- 2(N) |
---|---|---|---|---|---|---|---|---|
Rated load voltage | 200 to 480 VAC | |||||||
Operating voltage range | 180 to 528 VAC | |||||||
Rated load current *1 | 15 A (at 40 ° C) | 25 A (at 40 ° C) | 35 A (at 25 ° C) | 45 A (at 25 ° C) | ||||
Minimum load current | 0.5 A | |||||||
Inrush current resistance (peak value) |
220 A (60 Hz, 1 cycle) |
440 A (60 Hz, 1 cycle) |
||||||
Permissible I2t (reference value) | 260A2s | 1,260A2s | ||||||
Applicable load (resistive load: AC1 class) *2 |
12.5 kW (at 480 VAC) |
20.7 kW (at 480 VAC) |
29.0 kW (at 480 VAC) |
37.4 kW (at 480 VAC) |
*1. The applicable load current depends on the ambient temperature. For details, refer to Load Current vs. Ambient
Temperature in Engineering Data on Data Sheet.
*2. Applicable Load
Use the following formula to calculate the maximum total capacity of a heater load for a three-phase balanced load
with delta connections.
Model | G3PE- 215B- 3H |
G3PE- 215B- 2H |
G3PE- 225B- 3HH |
G3PE- 225B- 2H |
G3PE- 235B- 3H |
G3PE- 235B- 2H |
G3PE- 245B- 3H |
G3PE- 245B- 2H |
---|---|---|---|---|---|---|---|---|
Rated load voltage | 100 to 240 VAC | |||||||
Operating voltage range | 75 to 264 VAC | |||||||
Rated load current * | 15 A (at 40 ° C) | 25 A (at 40 ° C) | 35 A (at 25 ° C) | 45 A (at 25 ° C) | ||||
Minimum load current | 0.2 A | 0.5 A | ||||||
Inrush current resistance (peak value) |
150 A (60 Hz, 1 cycle) |
220 A (60 Hz, 1 cycle) |
440 A (60 Hz, 1 cycle) |
|||||
Permissible I2t (reference value) | 121A2s | 260A2s | 1,260A2s | |||||
Applicable load (resistive load: AC1 class) |
Refer to Engineering Data on Data Sheet. |
Model | G3PE- 515B- 3H |
G3PE- 515B- 2H |
G3PE- 525B- 3H |
G3PE- 525B- 2H |
G3PE- 535B- 3H |
G3PE- 535B- 2H |
G3PE- 545B- 3H |
G3PE- 545B- 2H |
---|---|---|---|---|---|---|---|---|
Rated load voltage | 200 to 480 VAC | |||||||
Operating voltage range | 180 to 528 VAC | |||||||
Rated load current * | 15 A (at 40 ° C) | 25 A (at 40 ° C) | 35 A (at 25 ° C) | 45 A (at 25 ° C) | ||||
Minimum load current | 0.5 A | |||||||
Inrush current resistance (peak value) |
220 A (60 Hz, 1 cycle) |
440 A (60 Hz, 1 cycle) |
||||||
Permissible I2t (reference value) | 260A2s | 1,260A2s | ||||||
Applicable load (resistive load: AC1 class) |
Refer to Engineering Data on Data Sheet. |
* The rated load current depends on the heat sink or radiator that is mounted. It also depends on the ambient
temperature.
For details, refer to Load Current vs. Ambient Temperature in Engineering Data on Data Sheet.
Model | G3PE- 215B- 3(N) |
G3PE- 215B- 2(N) |
G3PE- 225B- 3(N) |
G3PE- 225B- 2(N) |
G3PE- 235B- 3(N) |
G3PE- 235B- 2(N) |
G3PE- 245B- 3(N) |
G3PE- 245B- 2(N) |
---|---|---|---|---|---|---|---|---|
Operate time | 1/2 of load power source cycle + 1 ms max. | |||||||
Release time | 1/2 of load power source cycle + 1 ms max. | |||||||
Output ON voltage drop |
1.6 V (RMS) max. | |||||||
Leakage current * | 10 mA max. (at 200 VAC) | |||||||
Insulation resistance |
100 M Ω min. (at 500 VDC) | |||||||
Dielectric strength | 2,500 VAC, 50/60 Hz for 1 min | |||||||
Vibration resistance |
DIN Track mounting: 10 to 55 to 10 Hz, 0.175-mm single amplitude (0.35-mm double amplitude) Screw mounting: 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) |
|||||||
Shock resistance | 294 m/s2 (reverse mounting: 98 m/s2) | |||||||
Ambient storage temperature |
- 30 to 100 ° C (with no icing or condensation) | |||||||
Ambient operating temperature |
- 30 to 80 ° C (with no icing or condensation) | |||||||
Ambient operating humidity |
45% to 85% | |||||||
Weight | Approx. 1.25 kg | Approx. 1.45 kg |
Approx. 1.25 kg |
Approx. 1.65 kg |
Approx. 1.45 kg |
Approx. 2.0 kg |
Approx. 1.65 kg |
Model | G3PE- 515B- 3(N) |
G3PE- 515B- 2(N) |
G3PE- 525B- 3(N) |
G3PE- 525B- 2(N) |
G3PE- 535B- 3(N) |
G3PE- 535B- 2(N) |
G3PE- 545B- 3(N) |
G3PE- 545B- 2(N) |
---|---|---|---|---|---|---|---|---|
Operate time | 1/2 of load power source cycle + 1 ms max. | |||||||
Release time | 1/2 of load power source cycle + 1 ms max. | |||||||
Output ON voltage drop |
1.8 V (RMS) max. | |||||||
Leakage current * | 20 mA max. (at 480 VAC) | |||||||
Insulation resistance |
100 M Ω min. (at 500 VDC) | |||||||
Dielectric strength | 2,500 VAC, 50/60 Hz for 1 min | |||||||
Vibration resistance |
DIN Track mounting: 10 to 55 to 10 Hz, 0.175-mm single amplitude (0.35-mm double amplitude) Screw mounting: 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) |
|||||||
Shock resistance | 294 m/s2 (reverse mounting: 98 m/s2) | |||||||
Ambient storage temperature |
- 30 to 100 ° C (with no icing or condensation) | |||||||
Ambient operating temperature |
- 30 to 80 ° C (with no icing or condensation) | |||||||
Ambient operating humidity |
45% to 85% | |||||||
Weight | Approx. 1.25 kg | Approx. 1.45 kg |
Approx. 1.25 kg |
Approx. 1.65 kg |
Approx. 1.45 kg |
Approx. 2.0 kg |
Approx. 1.65 kg |
* The leakage current of phase S will be approximately √3 times larger if the 2-element model is used.
Model | G3PE- 215B- 3H |
G3PE- 215B- 2H |
G3PE- 225B- 3H |
G3PE- 225B- 2H |
G3PE- 235B- 3H |
G3PE- 235B- 2H |
G3PE- 245B- 3H |
G3PE- 245B- 2H |
---|---|---|---|---|---|---|---|---|
Operate time | 1/2 of load power source cycle + 1 ms max. | |||||||
Release time | 1/2 of load power source cycle + 1 ms max. | |||||||
Output ON voltage drop | 1.6 V (RMS) max. | |||||||
Leakage current * | 10 mA max. (at 200 VAC) | |||||||
Insulation resistance | 100 M Ω min. (at 500 VDC) | |||||||
Dielectric strength | 2,500 VAC, 50/60 Hz for 1 min | |||||||
Vibration resistance | 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) | |||||||
Shock resistance | Destruction: 294 m/s2 | |||||||
Ambient storage temperature | - 30 to 100 ° C (with no icing or condensation) | |||||||
Ambient operating temperature | - 30 to 80 ° C (with no icing or condensation) | |||||||
Ambient operating humidity | 45% to 85% | |||||||
Weight | Approx. 300 g |
Model | G3PE- 515B- 3H |
G3PE- 515B- 2H |
G3PE- 525B- 3H |
G3PE- 525B- 2H |
G3PE- 535B- 3H |
G3PE- 535B- 2H |
G3PE- 545B- 3H |
G3PE- 545B- 2H |
---|---|---|---|---|---|---|---|---|
Operate time | 1/2 of load power source cycle + 1 ms max. | |||||||
Release time | 1/2 of load power source cycle + 1 ms max. | |||||||
Output ON voltage drop | 1.8 V (RMS) max. | |||||||
Leakage current * | 20 mA max. (at 480 VAC) | |||||||
Insulation resistance | 100 M Ω min. (at 500 VDC) | |||||||
Dielectric strength | 2,500 VAC, 50/60 Hz for 1 min | |||||||
Vibration resistance | 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) | |||||||
Shock resistance | Destruction: 294 m/s2 | |||||||
Ambient storage temperature | - 30 to 100 ° C (with no icing or condensation) | |||||||
Ambient operating temperature | - 30 to 80 ° C (with no icing or condensation) | |||||||
Ambient operating humidity | 45% to 85% | |||||||
Weight | Approx. 300 g |
* The leakage current of phase S will be approximately √3 times larger if the 2-element model is used.
Model | Weight |
---|---|
Y92B-P50 | Approx. 450 g |
Y92B-P100 | Approx. 450 g |
Y92B-P150 | Approx. 600 g |