Best-selling, general-purpose relays that can be selected based on operating environment and application
Ngan Anh Phat Co., Ltd specializes in providing genuine products MY Miniature Power Relays from the manufacturer Omron, originating from Japan, to the Vietnamese market.
•Wiring work can be shortened by as much as 60%* compared to conventional screw terminal sockets by combining with push-in plus terminal sockets (PYF-[]-PU) that feature light insertion force and strong pull-out strength to achieve less wiring work.
• In addition to our standard type (MY), an abundant lineup of models including latching relays that retain contact operation status (MYK) and sealed relays suitable for environments where dust and corrosive gases are present (MYQ/MYH) are also available.
• Selection is possible to suit the application, such as models with operation indicators and models with latching levers (MY plug-in terminals).
* When both push-in plus terminals and screw terminal sockets are combined with plug-in terminal types (according to actual OMRON measurements as of November 2015)
Terminal Type | Classification | Number of poles |
Contacts | Without operation indicator |
With operation indicator |
---|---|---|---|---|---|
Plug-in terminals | Standard models | 2 | Single | MY2 | MY2N |
4 | Single | MY4 | MY4N | ||
Bifurcated | MY4Z | MY4ZN | |||
Models with built-in diode for coil surge absorption (DC coil specification only) |
2 | Single | MY2-D | MY2N-D2 | |
4 | Single | MY4-D | MY4N-D2 | ||
Bifurcated | MY4Z-D | MY4ZN-D2 | |||
Models with built-in CR circuit for coil surge absorption (AC coil specification only) |
2 | Single | MY2-CR | MY2N-CR | |
4 | Single | MY4-CR | MY4N-CR | ||
Bifurcated | MY4Z-CR | MY4ZN-CR |
Item | Rated current (mA) |
Coil resistance (Ω) |
Coil inductance (H) | Must operate voltage (V) |
Must release voltage (V) |
Maximum voltage (V) |
Power consumption (VA, W) |
|||
---|---|---|---|---|---|---|---|---|---|---|
Rated voltage (V) |
50 Hz | 60 Hz | Armature OFF |
Armature ON |
||||||
AC | 12 | 106.5 | 91 | 46 | 0.17 | 0.33 | 80% max. *1 |
30% min. *2 |
110% of rated voltage |
Approx. 0.9 to 1.3 (at 60 Hz) |
24 | 53.8 | 46 | 180 | 0.69 | 1.3 | |||||
100/110 | 11.7/12.9 | 10/11 | 3,750 | 14.54 | 24.6 | |||||
110/120 | 9.9/10.8 | 8.4/9.2 | 4,430 | 19.2 | 32.1 | |||||
200/220 | 6.2/6.8 | 5.3/5.8 | 12,950 | 54.75 | 94.07 | |||||
220/240 | 4.8/5.3 | 4.2/4.6 | 18,790 | 83.5 | 136.4 | |||||
DC | 12 | 72.7 | 165 | 0.73 | 1.37 | 10% min. *2 |
Approx. 0.9 | |||
24 | 36.3 | 662 | 3.2 | 5.72 | ||||||
48 | 17.6 | 2,725 | 10.6 | 21.0 | ||||||
100/110 | 8.7/9.6 | 11,440 | 45.6 | 86.2 |
Terminal Type | Classification | Number of poles |
Contacts | Without operation indicator |
With operation indicator |
---|---|---|---|---|---|
Plug-in terminals | Standard models | 2 | Bifurcated | MY2Z | MY2ZN |
Models with built-in diode for coil surge absorption (DC coil specification only) |
2 | Bifurcated | MY2Z-D | MY2ZN-D2 | |
3 | Single | MY3-D | MY3N-D2 | ||
Models with built-in CR circuit for coil surge absorption (AC coil specification only) |
2 | Bifurcated | MY2Z-CR | MY2ZN-CR |
Item | Rated current (mA) |
Coil resistance (Ω) |
Coil inductance (H) | Must operate voltage (V) |
Must release voltage (V) |
Maximum voltage (V) |
Power consumption (VA, W) |
|||
---|---|---|---|---|---|---|---|---|---|---|
Rated voltage (V) |
50 Hz | 60 Hz | Armature OFF |
Armature ON |
||||||
AC | 12 | 106.5 | 91 | 46 | 0.17 | 0.33 | 80% max. *1 |
30% min. *2 |
110% of rated voltage |
Approx. 0.9 to 1.3 (at 60 Hz) |
24 | 53.8 | 46 | 180 | 0.69 | 1.3 | |||||
100/110 | 11.7/12.9 | 10/11 | 3,750 | 14.54 | 24.6 | |||||
110/120 | 9.9/10.8 | 8.4/9.2 | 4,430 | 19.2 | 32.1 | |||||
200/220 | 6.2/6.8 | 5.3/5.8 | 12,950 | 54.75 | 94.07 | |||||
220/240 | 4.8/5.3 | 4.2/4.6 | 18,790 | 83.5 | 136.4 | |||||
DC | 12 | 75 | 160 | 0.73 | 1.37 | 10% min. *2 |
Approx. 0.9 | |||
24 | 36.9 | 650 | 3.2 | 5.72 | ||||||
48 | 18.5 | 2,600 | 10.6 | 21.0 | ||||||
100/110 | 9.1/10 | 11,000 | 45.6 | 86.2 |
Terminal Type | Classification | Number of poles | Contacts | With latching lever |
---|---|---|---|---|
Plug-in terminals | Standard models | 2 | Single | MY2IN(S) |
4 | Single | MY4IN(S) | ||
Bifurcated | MY4ZIN(S) | |||
Models with built-in diode for coil surge absorption (DC coil specification only) |
2 | Single | MY2IN-D2(S) | |
4 | Single | MY4IN-D2(S) | ||
Bifurcated | MY4ZIN-D2(S) | |||
Models with built-in CR circuit for coil surge absorption (AC coil specification only) |
2 | Single | MY4IN-CR(S) | |
4 | Bifurcated | MY4ZIN-CR(S) |
Item | Rated current (mA) |
Coil resistance (Ω) |
Coil inductance (H) | Must operate voltage (V) |
Must release voltage (V) |
Maximum voltage (V) |
Power consumption (VA, W) |
|||
---|---|---|---|---|---|---|---|---|---|---|
Rated voltage (V) |
50 Hz | 60 Hz | Armature OFF |
Armature ON |
||||||
AC | 100/110 | 11.7/12.9 | 10/11 | 3,750 | 14.54 | 24.6 | 80% max. *1 |
30% min. *2 |
110% of rated voltage |
Approx. 0.9 to 1.3 (at 60 Hz) |
200/220 | 6.2/6.8 | 5.3/5.8 | 12,950 | 54.75 | 94.07 | |||||
DC | 12 | 75 | 160 | 0.73 | 1.37 | 10% min. *2 |
Approx. 0.9 | |||
24 | 37.7 | 636 | 3.2 | 5.72 | ||||||
48 | 18.8 | 2,560 | 10.6 | 21 |