HMI V9071iWLD FUJI ELECTRIC

Price :
Contact
Quantity :
Status :
In Stock
Request a Quote
Share:
  • Origin
    JAPAN
  • Guarantee
    12 MONTHS
DO YOU NEED SUPPORT ?

HMI V9071iWLD FUJI ELECTRIC

Our company, Ngan Anh Phat Co., Ltd., specializes in distributing and supplying the HMI V9071iWLD FUJI ELECTRIC to the Vietnamese market.

Key features of the HMI V9071iWLD FUJI ELECTRIC

  • The displayed image can be magnified up to 200% by pinching out*2 and reduced to the original size by pinching in.  
  • You can view a specific part of a magnified image in close-up while scrolling around the screen.  
  • The entire area of a large image can be easily reviewed by scrolling the screen without the need for switching.  
  • The navigation window helps you instantly recognize the currently displayed position

Specifications

V9071iW
Power supply Rated voltage 24V DC
Permissible range of voltage DC: ±10%
Permissible momentary power failure DC within 1ms
Demand (maximum rating) DC: 22W or less
Insulation resistance   DC500V 10MΩ or more
Physical environment Ambient temperature 0~50℃ *1
Ambient humidity 85%RH or less (without dew condensation) *1
Operation altitude 2,000 meters or lower
Atmosphere Not to be exposed to corrosive gas, or conductive dust
Storage temperature -10~60℃ *1
Storage humidity 85%RH or less (without dew condensation) *1
Overvoltage category Category II
Pollution degree Pollution degree 2
Mechanical operating conditions Resistance to oscillation Complies with JIS B 3502 (IEC61131-2) Vibration frequency: 5~9Hz, pulsating with:3.5mm,
9~150Hz, Acceleration: 9.8m/s2(1G),X,Y,Z: 3 directions (10 times each)
Resistance to shock Complies with JIS B 3502 (IEC61131-2) Peak acceleration: 147m/s2(15G), X,Y,Z:
3 directions, three times each (18 times in total)
Electric operating conditions Resistance to noise Noise voltage: 1,000Vp-p, pulse width: 1μs, pulse rise time: 1ns
Resistance to static discharge Complies with IEC61000-4-2, contact: 6kV, air: 8kV
Installation conditions Grounding Grounding resistance: Less than 100Ω, FG/SG separation
Structure Front panel:Complies with IP66, Type 4X/13 (when waterproof gasket is installed)
Rear cover:Complies with IP20
Form: Single unit, Installation method: Panel mounting
Cooling system Natural air cooling
Dimensions W*H*D(mm) 201.6×147.6×60.3
Panel cutout (mm) 187.2×133.4(+0.5/-0)
Weight
(display only)
Approx. 1.0 kg
Case color   Light gray
Material   PC
  • *1: Use at a wet-bulb temperature of 39°C or less because higher temperatures may cause failure.

Performance Specifications

Screen memory (FROM)   64MB
Backup memory (SRAM)   800KB
Display Display device TFT color LCD
Resolution 800×480
Display size 7″wide
Colors 16.7 million *2
Backlight LED
Backlight life 100,000 hours
Touch switch Type Capacitance
External interface D-Sub 9-pin (CN1)*3 RS-232C, RS-485(two-wire system), RS-422(four-wire system), Asynchronous type,
Data length: 7,8 bits, Parity: even, odd, none,
Stop bit: 1, 2 bits, Baud rate: 4800, 9600, 19200, 38400, 57600, 76800, 115200 bps
Modular 8-pin
(MJ1/MJ2)
RS-232C, RS-485(two-wire system), RS-422(four-wire system)*4 , Asynchronous type,
Data length: 7,8 bits, Parity: even, odd, none, Stop bit: 1, 2 bits, Baud rate: 4800, 9600,
19200, 38400, 57600, 76800, 115200, 187500*5 bps
SD card One card slot provided as standard
Ethernet 2ch,
Baud rate: 100Mbps,
10Mbps
Wireless LAN*6 Complies with IEEE802.11b/g/n(2.4GHz)
USB Type A,Type mini-B(Ver.2.0)
Sound output -
Clock Backup period 5 years (Ambient temperature 25°C)
Calendar accuracy Gap ±90 sec. per month (Ambient temperature 25°C, when power is not supplied)
Standard CE marking EN61000-6-2,EN61000-6-4
UL・cUL UL61010-1、UL61010-2-201※7
KC Compliant
Radio Act*6 Japan:TELEC
USA:FCC
Canada:IC RSS
Europe:RE
South Korea:KC
Classification Standard   -
  • *2: For displaying pictures, 3D parts,video, and RGB input (excluding high-speed mode) only. Other parts are displayed in 65,536 colors.
  • *3: Optional unit(DUR-00) is required for the V9071iW and V9060iTD.
  • *4: 187,500 bps (four-wire system) for the V9071iW and V9060iTD MJ2 only.
  • *5: Only for Siemens MPI (Incompatible with DUR-00).
  • *6: Wireless LAN-compatible products only.
  • *7: Only for Hardware Ver. f or later. Applicable standard for Hardware Ver. a to e is UL 508